TAP Services(865) 919-6674

26209-11 Grounding and Bonding

1. A short circuit is a conducting connection between ________.

Question 1 of 35

2. A ground test utilizing an earth ground resistance tester is known as the ________.

Question 2 of 35

3. Grounding requirements for AC systems are contained in ________.

Question 3 of 35

4. The continuity between service equipment and enclosures is maintained by ________.

Question 4 of 35

5. Where a main bonding jumper is required by the NEC®, the jumper cannot be less than what percentage of the area of the largest phase conductor?

Question 5 of 35

6. In a separately derived system, the equipment bonding jumper connects ________.

Question 6 of 35

7. Which transformer-supplied system must be grounded if the supply voltage to the transformer exceeds 150V?

Question 7 of 35

8. The minimum diameter of galvanized pipe allowed for a grounding electrode is ________.

Question 8 of 35

9. Which of the following is true of the neutral in a grounded system?

Question 9 of 35

10. Rod, pipe, and plate electrodes must have a resistance to ground of at least ________.

Question 10 of 35

11. Ultimately, the ground fault is cleared when the ________.

Question 11 of 35

12. Which of the following is an NEC® requirement for grounding and bonding?

Question 12 of 35

13. The bonding jumper for multiple disconnecting means is located ________.

Question 13 of 35

14. The maximum value of a short circuit current from line-to-ground ________.

Question 14 of 35

15. The size of the equipment grounding conductor (EGC) is determined by the ________.

Question 15 of 35

16. Which of the following is used to secure equipment grounding conductors to metallic outlet boxes?

Question 16 of 35

17. When a ground rod is installed, the top of the rod must be positioned ________.

Question 17 of 35

18. A ground ring consisting of 20' of No. 2 bare copper must be buried no less than ________.

Question 18 of 35

19. Which of the following describes a ground fault?

Question 19 of 35

20. The key to successfully clearing ground fault currents is ________.

Question 20 of 35

21. The requirements for grounding of services are located in ________.

Question 21 of 35

22. The minimum length allowed for driven ground rods under normal conditions is ________.

Question 22 of 35

23. Which of the following describes bonding?

Question 23 of 35

24. If Single-Gang Nail-On non-metallic boxes are used with NM cable, which of the following is true?

Question 24 of 35

25. A separately derived system is a premises wiring system that is ________.

Question 25 of 35

26. Plate electrodes made of copper must be at least ________.

Question 26 of 35

27. Where there is a requirement to add a second grounding electrode, the two electrodes must be spaced at least ________.

Question 27 of 35

28. Which of the following must be connected to the neutral terminal bus of a main distribution panel?

Question 28 of 35

29. Equipment grounding refers to connecting the normally noncurrent-carrying metal parts of equipment to the system grounded conductor and/or ________.

Question 29 of 35

30. To be effective, a grounding system must limit the voltage on the electrical system and protect it from ________.

Question 30 of 35

31. If the neutral in a grounded system is not needed for voltage requirements, it ________.

Question 31 of 35

32. Which type of system is required to be grounded?

Question 32 of 35

33. System grounding relates to the ________.

Question 33 of 35

34. An acceptable grounding electrode is a(n) ________.

Question 34 of 35

35. Which of the following must have at least 2 square feet of surface area exposed to the surrounding earth?

Question 35 of 35